for LSA-PLUS strips (CLSA)
CLSA-TLF
Order number: A05173for LSA-PLUS separating strips
- combination of coarse and fine protection of 2-core telecommunication lines
- installation close to protected equipment
- for protection of telecommunication lines against impact of surge voltage
- coarse and fine surge protection in differential mode (core – core) and coarse protection in common mode (core – PE)
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | C2,C3 | |
Location of SPD | ST 2+3 | |
Mounting | LSA disconnection rail | |
Maximum operating voltage | Uc | 120.00 V AC |
Maximum operating voltage | Uc | 170.00 V DC |
Nominal load current | IL | 0.500 A |
Serial resistance per core | R | 1.60 Ω |
C2 nominal discharge current (8/20 µs) per core | In | 5.00 kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10.00 kA |
C2 voltage protection level mode core-PE at In | Up | 400 V |
C2 voltage protection level mode core-core at In | Up | 310 V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350 V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 230 V |
Response time core-core | ta | 1 ns |
Response time core-PE | ta | 100 ns |
Connection (input - output) | LSA disconnection rail | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 70 °C | |
According to standard | EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001625 | |
Accessories | grounding rail | |
Customs tariff number | 85363010 | |
EAN | 8595090551737 |