Build in
DA-275 CZS
Order number: A01916remote fault signalling
- SPD for additional installation to devices or equipments
- installation to LV installations, close to protected equipment
- for protection of all LV equipments against surge voltage
- non-symetrical connection
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T3 | |
Mounting | installation box | |
Nominal voltage | Un | 230 V AC |
Maximum operating voltage | Uc | 275.00 V AC |
Type of network | TN | |
Maximum overcurrent protection | B 16 A | |
Short-circuit current rating | ISCCR | 1.5 kA |
Nominal discharge current (8/20 µs) L-N | In | 3.00 kA |
Nominal discharge current (8/20 µs) N-PE | In | 3.00 kA |
Test voltage L-N | Uoc | 6.0 kV |
Test voltage N-PE | Uoc | 6.0 kV |
Voltage protection level mode L-N | Up | 1.35 kV |
Voltage protection level mode L-PE | Up | 1.50 kV |
Voltage protection level mode N-PE | Up | 1.50 kV |
Response time L-N | ta | 25 ns |
Response time N-PE | ta | 100 ns |
TOV 5 s L-N | 335 V | |
Fault indication | open contact | |
Remote indication | potential-free open contact | |
Remote indication contacts | 230V/0,5A AC,24V/0,5A DC | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000942 | |
Customs tariff number | 85363010 | |
EAN | 8595090519164 |