ST2+3 (DM) - terminal block
DMJ-012/2-RS
Order number: A05144coupling impedance (resistance), screw terminals
- coarse and fine surge protection for two 1-core signalling networks
- installation close to protected equipment
- for protection of communication interfaces and control circuits of I&C, electronic security and fire detection systems, etc. against impact of surge voltage
- coarse and fine surge protection in common mode (core – PE)
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | C2,C3 | |
Location of SPD | ST 2+3 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 12 V DC |
Maximum operating voltage | Uc | 11.00 V AC |
Maximum operating voltage | Uc | 16.00 V DC |
Nominal load current | IL | 0.500 A |
Treshold frequency core-core | f | 2.00 MHz |
Serial resistance per core | R | 1.60 Ω |
D1 impulse discharge current (10/350 µs) per core | Iimp | 0.50 kA |
D1 total discharge current (10/350 µs) cores-PE | ITotal | 1.00 kA |
C2 nominal discharge current (8/20 µs) per core | In | 5.00 kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10.00 kA |
C2 voltage protection level mode core-PE at In | Up | 40 V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 20 V |
Response time core-PE | ta | 1 ns |
Connection (input - output) | terminals-terminals | |
Cross-section of connected conductors solid (min) | 0.14 mm2 | |
Cross-section of connected conductors solid (max) | 4.00 mm2 | |
Cross-section of connected conductors stranded (min) | 0.14 mm2 | |
Cross-section of connected conductors stranded (max) | 2.50 mm2 | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 70 °C | |
According to standard | EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001625 | |
Customs tariff number | 85363010 | |
EAN | 8595090551447 |