MOV
FLP-12,5 V/3S+1
Order number: A03428pluggable module, visual fault signalling, module locking, remote fault signalling
- combination of varistor lightning current arrester and encapsulated efficiency spark gap, connected in the 3+1 mode
- installation at the boundary of zones LPZ 0 and LPZ 1 or higher, for objects in LPL III and IV
- for protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T1,T2 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 230 V AC |
Maximum operating voltage L-N | Uc | 275.00 V AC |
Maximum operating voltage N-PE | Uc | 255.00 V AC |
Type of network | TT | |
Maximum overcurrent protection | 160 A gL/gG | |
Short-circuit current rating | ISCCR | 50.0 kA |
Total discharge current (10/350 µs) | ITotal(10/350) | 50.00 kA |
Lightning impulse current (10/350 µs) L-N | Iimp | 12.50 kA |
Lightning impulse current (10/350 µs) N-PE | Iimp | 50.00 kA |
Nominal discharge current (8/20 µs) L-N | In | 30.00 kA |
Nominal discharge current (8/20 µs) N-PE | In | 50.00 kA |
Maximum discharge current (8/20 µs) L-N | Imax | 60.00 kA |
Maximum discharge current (8/20 µs) N-PE | Imax | 100.00 kA |
Voltage protection level mode L-N | Up | 1.50 kV |
Voltage protection level mode L-PE | Up | 1.50 kV |
Voltage protection level mode N-PE | Up | 1.50 kV |
Voltage protection level at 5 kA L-N | Up | 0.90 kV |
Ability to independently switch off the following current N-PE | Ifi | 0.1 kA |
Response time L-N | ta | 25 ns |
Response time N-PE | ta | 100 ns |
TOV 5 s L-N | 335 V | |
TOV characteristic (TOV 5 s) | withstand | |
TOV 200 ms N-PE | 1 200 V | |
TOV characteristic (TOV 200 ms) | withstand | |
Cross-section of connected conductors solid (min) | 1.00 mm2 | |
Cross-section of connected conductors solid (max) | 35.00 mm2 | |
Cross-section of connected conductors stranded (min) | 1.00 mm2 | |
Cross-section of connected conductors stranded (max) | 25.00 mm2 | |
Cross-section of remote indication conductors solid (max) | 1.5 mm2 | |
Cross-section of remote indication conductors stranded (max) | 1.5 mm2 | |
Fault indication L-N | red indication field | |
Remote indication | potential-free change-over contact | |
Remote indication contacts | 250V/0,5A AC,250V/0,1A DC | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC001457 | |
Plug module | FLP-12,5 V/0 | |
Customs tariff number | 85363090 | |
EAN | 8595090534280 |