MOV

SLP-150 V/2 S

Order number: A07446

pluggable module, visual fault signalling, remote fault signalling

  • two-pole varistor surge arrester
  • installation to LV installations, especially to sub-distribution boards in TN-S systems
  • for protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages

Technical parameters

Parameter name Parameter value
Type of SPD T2
Mounting DIN rail 35 mm
Nominal voltage Un 120 V AC
Maximum operating voltage Uc 150.00 V AC
Maximum operating voltage Uc 200.00 V DC
Type of network TN
Maximum overcurrent protection 160 A gL/gG
Short-circuit current rating ISCCR 50.0 kA
Residual current IPE 0.350 mA
Nominal discharge current (8/20 µs) In 15.00 kA
Maximum discharge current (8/20 µs) Imax 40.00 kA
Voltage protection level Up 0.74 kV
Voltage protection level at 5 kA Up 0.60 kV
Response time ta 25 ns
TOV 5 s L-N 175 V
TOV characteristic (TOV 5 s) withstand
Cross-section of connected conductors solid (min) 4.00 mm2
Cross-section of connected conductors solid (max) 35.00 mm2
Cross-section of connected conductors stranded (min) 4.00 mm2
Cross-section of connected conductors stranded (max) 25.00 mm2
Cross-section of remote indication conductors solid (max) 1.5 mm2
Cross-section of remote indication conductors stranded (max) 1.5 mm2
Fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250V/0,5A AC,250V/0,1A DC
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
Humidity 5 - 95 %
According to standard EN 61643-11:2012, IEC 61643-11:2011
ETIM Class EC000941
Plug module SLP-150 V/0
Customs tariff number 85363030
EAN 8595090574460

Files for download

  • Product dimensions

  • Basic circuit diagram

Replacement module