MOV
SLP-440 V/3
Order number: A01910pluggable module, visual fault signalling, module locking
- three-pole varistor surge arrester
- installation to LV installations, especially to sub-distribution boards in 400/690 V AC TN-C systems or TN-S without neutral conductor, eventually in IT system 400 V AC
- for protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T2 | |
Mounting | DIN rail 35 mm | |
Maximum operating voltage | Uc | 440.00 V AC |
Maximum operating voltage | Uc | 585.00 V DC |
Type of network | TN | |
Maximum overcurrent protection | 125 A gL/gG | |
Short-circuit current rating | ISCCR | 25.0 kA |
Nominal discharge current (8/20 µs) | In | 20.00 kA |
Maximum discharge current (8/20 µs) | Imax | 40.00 kA |
Voltage protection level | Up | 1.90 kV |
Voltage protection level at 5 kA | Up | 1.50 kV |
Response time | ta | 25 ns |
Cross-section of connected conductors solid (min) | 1.00 mm2 | |
Cross-section of connected conductors solid (max) | 35.00 mm2 | |
Cross-section of connected conductors stranded (min) | 1.00 mm2 | |
Cross-section of connected conductors stranded (max) | 25.00 mm2 | |
Fault indication | red indication field | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000941 | |
Plug module | SLP-440 V/0 | |
Customs tariff number | 85363030 | |
EAN | 8595090519102 |