MOV
SLP-600-V/3YS-IT
Order number: A04199pluggable module, visual fault signalling, module locking
- three-pole varistor surge arrester
- installation to LV installations, especially to sub-distribution boards in IT systems
- for protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
- remote fault signalling
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T2 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 400,00–690,00 V AC |
Maximum operating voltage | Uc | 760.00 V AC |
Type of network | IT | |
Maximum overcurrent protection | 100 A gL/gG | |
Short-circuit current rating | ISCCR | 25.0 kA |
Residual current | IPE | 0.200 mA |
Nominal discharge current (8/20 µs) L-PE | 20.00 kA | |
Maximum discharge current (8/20 µs) L-PE | 40.00 kA | |
Total discharge current (8/20 µs) | ITotal(8/20) | 60.00 kA |
Voltage protection level mode L-PE | Up | 3.40 kV |
Voltage protection level at 5 kA L-PE | 2.50 kV | |
Response time | ta | 100 ns |
TOV 200 ms L-PE | 1 960 V | |
TOV characteristic (TOV 200 ms) | withstand | |
Cross-section of connected conductors solid (min) | 1.00 mm2 | |
Cross-section of connected conductors solid (max) | 35.00 mm2 | |
Cross-section of connected conductors stranded (min) | 1.00 mm2 | |
Cross-section of connected conductors stranded (max) | 25.00 mm2 | |
Cross-section of remote indication conductors solid (max) | 1.5 mm2 | |
Cross-section of remote indication conductors stranded (max) | 1.5 mm2 | |
Fault indication | red indication field | |
Remote indication | potential-free change-over contact | |
Remote indication contacts | 250V/0,5A AC,250V/0,1A DC | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000941 | |
Plug module | SLP-600 V/0 | |
Customs tariff number | 85363090 | |
EAN | 8595090541998 |