MOV

SLP-600-V/3YS-IT

Order number: A04199

pluggable module, visual fault signalling, module locking

  • three-pole varistor surge arrester
  • installation to LV installations, especially to sub-distribution boards in IT systems
  • for protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
  • remote fault signalling

Technical parameters

Parameter name Parameter value
Type of SPD T2
Mounting DIN rail 35 mm
Nominal voltage Un 400,00–690,00 V AC
Maximum operating voltage Uc 760.00 V AC
Type of network IT
Maximum overcurrent protection 100 A gL/gG
Short-circuit current rating ISCCR 25.0 kA
Residual current IPE 0.200 mA
Nominal discharge current (8/20 µs) L-PE 20.00 kA
Maximum discharge current (8/20 µs) L-PE 40.00 kA
Total discharge current (8/20 µs) ITotal(8/20) 60.00 kA
Voltage protection level mode L-PE Up 3.40 kV
Voltage protection level at 5 kA L-PE 2.50 kV
Response time ta 100 ns
TOV 200 ms L-PE 1 960 V
TOV characteristic (TOV 200 ms) withstand
Cross-section of connected conductors solid (min) 1.00 mm2
Cross-section of connected conductors solid (max) 35.00 mm2
Cross-section of connected conductors stranded (min) 1.00 mm2
Cross-section of connected conductors stranded (max) 25.00 mm2
Cross-section of remote indication conductors solid (max) 1.5 mm2
Cross-section of remote indication conductors stranded (max) 1.5 mm2
Fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250V/0,5A AC,250V/0,1A DC
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
Humidity 5 - 95 %
According to standard EN 61643-11:2012, IEC 61643-11:2011
ETIM Class EC000941
Plug module SLP-600 V/0
Customs tariff number 85363090
EAN 8595090541998

Files for download

  • Product dimensions

  • Basic circuit diagram

Replacement module