Telecommunications

DL-TLF-UHF

Order number: A07084

surge protection for analog telephone line and xDSL

  • two-stage surge protection of analog telephone line and xDSL
  • installation at boundary LPZ 0 - 1 and higher
  • connection of metallic pair via screw terminals
  • working voltage up to 170 V DC

Technical parameters

Parameter name Parameter value
Type of SPD D1,C2,C3
Location of SPD ST 1+2+3
Mounting DIN rail 35 mm
Maximum operating voltage Uc 170.00 V DC
Serial resistance per core R 10.00 Ω
Nominal load current IL 0.300 A
C2 nominal discharge current (8/20 µs) core-core In 5.00 kA
D1 total discharge current (10/350 µs) cores-PE ITotal 5.00 kA
C2 voltage protection level mode core-core (@Uoc/In) Up 600,00 V (10 kV / 5 kA)
C2 voltage protection level mode core-PE (@Uoc/In) Up 900,00 V (10 kV / 5 kA)
C3 voltage protection level mode core-core (@In - 1 kV/µs) Up 250,00 V (10 A)
C3 voltage protection level mode core-PE (@In - 1 kV/µs) Up 550,00 V (10 A)
Response time core-core ta 1 ns
Response time core-PE ta 100 ns
Treshold frequency core-core f 150 MHz (@ −1 dB)
Insertion loss A <1 dB (@ 35 MHz)
Connection (input - output) terminals-terminals
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 70 °C
Humidity 5 - 95 %
According to standard EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class EC000943
Customs tariff number 85363010
EAN 8595090570844

Files for download

  • Product dimensions

  • Basic circuit diagram