SPD

DA-320-LED

Order number: A06740

fault signalling by supply interruption

  • surge protection especially for LED lights
  • installation close to protected equipment in LV power circuits
  • also for equipment in external part of building with low exposure level (according to IEEE C62.41.2)

Technical parameters

Parameter name Parameter value
Type of SPD T3
Mounting installation box
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 320.00 V AC
Nominal load current IL 5.000 A
Maximum overcurrent protection B 16 A
Short-circuit current rating ISCCR 1.5 kA
Nominal discharge current (8/20 µs) L-N In 3.00 kA
Nominal discharge current (8/20 µs) L+N-PE In 5.00 kA
Nominal discharge current (8/20 µs) N-PE In 3.00 kA
Test voltage L-N Uoc 6.0 kV
Test voltage L+N-PE Uoc 10.0 kV
Test voltage L-PE Uoc 6.0 kV
Test voltage N-PE Uoc 6.0 kV
Voltage protection level mode L-N Up 1.50 kV
Voltage protection level mode L-PE Up 1.50 kV
Voltage protection level mode N-PE Up 1.50 kV
Response time L-N ta 25 ns
Response time N-PE ta 100 ns
Fault indication loss of voltage
Remote indication potential open contact
Maximum current of signalling 1.00 A
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
Humidity 5 - 95 %
According to standard EN 61643-11:2012, IEC 61643-11:2011
ETIM Class EC000942
Customs tariff number 85363010
EAN 8595090567400

Files for download

  • Product dimensions

  • Basic circuit diagram