ST2+3 (DM) - plugable

DMG-024-V/1-4FR1-DIF

Order number: A06281

pluggable module, coupling impedance (R – resistance), shielding (G) separated from protective earth via GDT

  • coarse and fine surge protection for max. 4-core signalling lines
  • installation close to protected equipment
  • for protection of communication interfaces of I <(>&<)>C, electronic security and fire detection systems, etc. (mainly for RS-485 interfaces) against impact of surge voltage
  • coarse and fine surge protection only in differential mode (core – core)

Technical parameters

Parameter name Parameter value
Type of SPD C2
Location of SPD ST 2+3
Mounting DIN rail 35 mm
Nominal voltage Un 24 V DC
Maximum operating voltage Uc 25.00 V AC
Maximum operating voltage Uc 36.00 V DC
Nominal load current IL 1.000 A
Treshold frequency core-core f 6.00 MHz
Serial resistance per core R 0.80 Ω
C2 nominal discharge current (8/20 µs) GND-PE In 10.00 kA
C2 nominal discharge current (8/20 µs) per core In 10.00 kA
C3 voltage protection level mode GND-PE at 1 kV/µs Up 550.00 V
C3 voltage protection level mode core-core at 1 kV/µs Up 46 V
Response time core-core ta 1 ns
Response time GND-PE ta 100 ns
Connection (input - output) terminals-terminals
Cross-section of connected conductors solid (min) 0.14 mm2
Cross-section of connected conductors solid (max) 4.00 mm2
Cross-section of connected conductors stranded (min) 0.14 mm2
Cross-section of connected conductors stranded (max) 2.50 mm2
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 70 °C
According to standard EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class EC001625
Customs tariff number 85363010
EAN 8595090562818

Files for download

  • Product dimensions

  • Basic circuit diagram