Supply (DP and DMP) - with signalling line
DMP-024-V/1-FR1
Order number: A05799pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT
- combination of two-stage surge protection of 2-core signalling line in data part and surge protection for ELV in supply part
- installation close to protected equipment
- for protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Cross-section of connected conductors solid (min) | 0.14 mm2 | |
Cross-section of connected conductors solid (max) | 4.00 mm2 | |
Cross-section of connected conductors stranded (min) | 0.14 mm2 | |
Cross-section of connected conductors stranded (max) | 2.50 mm2 | |
Fault indication | red indicator | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 70 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001473 | |
Plug module | DMP-024-V/1-0 | |
Nominal voltage | Un | 24 V AC |
Maximum operating voltage | Uc | 25.00 V AC |
Maximum operating voltage | Uc | 36.00 V DC |
Nominal load current | IL | 16.000 A |
Maximum overcurrent protection | 16 A gL/gG nebo B 16 A | |
C2 nominal discharge current (8/20 µs) core-core | In | 2.00 kA |
Test voltage L+ - L- | 4.0 kV | |
Test voltage L+(L-)-PE | 4.0 kV | |
Test voltage M-PE | 4.0 kV | |
voltage protection level L+ - L- | 0.13 kV | |
voltage protection level L+(L-)-PE | 0.95 kV | |
voltage protection level M-PE | 0.75 kV | |
C2 voltage protection level mode M-PE at In | 750.00 V | |
C2 voltage protection level mode core-PE at In | Up | 950 V |
C2 voltage protection level mode core-core at In | Up | 230 V |
Response time L+ - L- | 25 ns | |
Response time L+(L-)-PE | 100 ns | |
Response time M-PE | 100 ns | |
Nominal voltage | Un | 24 V DC |
Maximum operating voltage | Uc | 25.00 V AC |
Maximum operating voltage | Uc | 36.00 V DC |
Nominal load current | IL | 1.000 A |
Treshold frequency core-core | f | 4.00 MHz |
Serial resistance per core | R | 0.80 Ω |
C2 nominal discharge current (8/20 µs) GND-PE | 10.00 kA | |
C2 nominal discharge current (8/20 µs) per core | In | 10.00 kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 20.00 kA |
C3 nominal discharge current (10/1000 µs) GND-PE | 10.00 A | |
C3 nominal discharge current (10/1000 µs) core-PE | 10.00 A | |
C3 nominal discharge current (10/1000 µs) core-core | In | 10 A |
C3 voltage protection level mode GND-PE at 1 kV/µs | 550.00 V | |
C3 voltage protection level mode core-GND at 1 kV/µs | 46.00 V | |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 46 V |
Response time core-core | ta | 1 ns |
Response time core-GND | 1 ns | |
Response time GND-PE | 100 ns | |
Customs tariff number | 85363010 | |
EAN | 8595090557999 |