Supply (DP and DMP) - with signalling line

DMP-024-V/1-FR1

Order number: A05799

pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT

  • combination of two-stage surge protection of 2-core signalling line in data part and surge protection for ELV in supply part
  • installation close to protected equipment
  • for protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage

Technical parameters

Parameter name Parameter value
Cross-section of connected conductors solid (min) 0.14 mm2
Cross-section of connected conductors solid (max) 4.00 mm2
Cross-section of connected conductors stranded (min) 0.14 mm2
Cross-section of connected conductors stranded (max) 2.50 mm2
Fault indication red indicator
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 70 °C
Humidity 5 - 95 %
According to standard EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class EC001473
Plug module DMP-024-V/1-0
Nominal voltage Un 24 V AC
Maximum operating voltage Uc 25.00 V AC
Maximum operating voltage Uc 36.00 V DC
Nominal load current IL 16.000 A
Maximum overcurrent protection 16 A gL/gG nebo B 16 A
C2 nominal discharge current (8/20 µs) core-core In 2.00 kA
Test voltage L+ - L- 4.0 kV
Test voltage L+(L-)-PE 4.0 kV
Test voltage M-PE 4.0 kV
voltage protection level L+ - L- 0.13 kV
voltage protection level L+(L-)-PE 0.95 kV
voltage protection level M-PE 0.75 kV
C2 voltage protection level mode M-PE at In 750.00 V
C2 voltage protection level mode core-PE at In Up 950 V
C2 voltage protection level mode core-core at In Up 230 V
Response time L+ - L- 25 ns
Response time L+(L-)-PE 100 ns
Response time M-PE 100 ns
Nominal voltage Un 24 V DC
Maximum operating voltage Uc 25.00 V AC
Maximum operating voltage Uc 36.00 V DC
Nominal load current IL 1.000 A
Treshold frequency core-core f 4.00 MHz
Serial resistance per core R 0.80 Ω
C2 nominal discharge current (8/20 µs) GND-PE 10.00 kA
C2 nominal discharge current (8/20 µs) per core In 10.00 kA
C2 total discharge current (8/20 µs) cores-PE ITotal 20.00 kA
C3 nominal discharge current (10/1000 µs) GND-PE 10.00 A
C3 nominal discharge current (10/1000 µs) core-PE 10.00 A
C3 nominal discharge current (10/1000 µs) core-core In 10 A
C3 voltage protection level mode GND-PE at 1 kV/µs 550.00 V
C3 voltage protection level mode core-GND at 1 kV/µs 46.00 V
C3 voltage protection level mode core-core at 1 kV/µs Up 46 V
Response time core-core ta 1 ns
Response time core-GND 1 ns
Response time GND-PE 100 ns
Customs tariff number 85363010
EAN 8595090557999

Files for download

  • Product dimensions

  • Basic circuit diagram

Replacement module