Specials - limiting current

DMS-024T

Order number: A06596

coupling impedance (resistance)

  • special two-stage surge protection of 2-core signalling line with current limiting
  • installation close to protected equipment
  • for protection of communication interfaces, mainly the measuring loops, of I<(>&<)>C, electronic security and fire detection systems, etc. against surge voltage where are long parallel lines with power network
  • coarse and fine surge protection in differential mode (core – core) and coarse surge protection in common mode (core – PE)

Technical parameters

Parameter name Parameter value
Type of SPD C2
Location of SPD ST 2+3
Mounting DIN rail 35 mm
Nominal voltage Un 24 V DC
Maximum operating voltage Uc 23.00 V AC
Maximum operating voltage Uc 33.00 V DC
Nominal load current IL 0.060 A
Treshold frequency core-core f 1.10 MHz
Serial resistance per core R 13.00 Ω
C2 nominal discharge current (8/20 µs) per core In 5.00 kA
C2 total discharge current (8/20 µs) cores-PE ITotal 10.00 kA
C2 voltage protection level mode core-PE at In Up 500 V
C2 voltage protection level mode core-core at In Up 75 V
Response time core-core ta 1 ns
Response time core-PE ta 100 ns
Connection (input - output) terminals
Cross-section of connected conductors solid (max) 2.50 mm2
Cross-section of connected conductors stranded (max) 2.50 mm2
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 70 °C
According to standard EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class EC001625
Customs tariff number 85363030
EAN 8595090565963

Files for download

  • Product dimensions

  • Basic circuit diagram