Combination type - T1+T2 (25 kA)
FLP-B+C-MAXI-VSF/1
Order number: A07116pluggable module, visual fault signalling, module locking, remote fault signalling
- high performance lightning current arrester
- installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards
- for protection against impact of direct or indirect lightning strikes in wide range of applications – office or industrial buildings
- no follow current, zero leakage current
- with integrated backup fuse
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T1,T2 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 230 V AC |
Maximum operating voltage | Uc | 260.00 V AC |
Type of network | TN | |
Maximum overcurrent protection | - | |
Short-circuit current rating | ISCCR | 50.0 kA |
Lightning impulse current (10/350 µs) | Iimp | 25.00 kA |
Nominal discharge current (8/20 µs) | In | 30.00 kA |
Voltage protection level | Up | 1.50 kV |
Response time | ta | 100 ns |
TOV 5 s L-N | 335 V | |
TOV characteristic (TOV 5 s) | withstand | |
TOV 120 min L-N | 440 V | |
TOV characteristic (120 min) | withstand | |
Cross-section of connected conductors solid (min) | 2.50 mm2 | |
Cross-section of connected conductors solid (max) | 50.00 mm2 | |
Cross-section of connected conductors stranded (min) | 2.50 mm2 | |
Cross-section of connected conductors stranded (max) | 35.00 mm2 | |
Cross-section of remote indication conductors solid (max) | 1.5 mm2 | |
Cross-section of remote indication conductors stranded (max) | 1.5 mm2 | |
Fault indication | red indication field | |
Remote indication | potential-free change-over contact | |
Remote indication contacts | 250V/0,5A AC,250V/0,1A DC | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC001457 | |
Plug module | FLP-B+C MAXI V/0 | |
Customs tariff number | 85363090 | |
EAN | 8595090571162 |