Supply (DP and DMP) - compact
DP-012-25
Order number: A06096visual fault singalling
- surge protection for all types of ELV electric and electronic equipments against surge voltage
- installation to LV installations, close to protected equipment
- for protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T3 | |
Location of SPD | ST 2 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 12 V AC |
Maximum operating voltage | Uc | 20.00 V AC |
Maximum operating voltage | Uc | 20.00 V DC |
Nominal load current | IL | 25.000 A |
Maximum overcurrent protection | 25 A gL/gG or C 25 A | |
C2 nominal discharge current (8/20 µs) per core | In | 2.00 kA |
Test voltage L+ - L- | 4.0 kV | |
Test voltage L+(L-)-PE | 4.0 kV | |
voltage protection level L+ - L- | 0.18 kV | |
voltage protection level L+(L-)-PE | 0.55 kV | |
C2 voltage protection level mode core-PE at In | Up | 550 V |
C2 voltage protection level mode core-core at In | Up | 180 V |
Response time L+ - L- | 25 ns | |
Response time L+(L-)-PE | 100 ns | |
Connection (input - output) | terminals-terminals | |
Cross-section of connected conductors solid (max) | 6.00 mm2 | |
Cross-section of connected conductors stranded (max) | 6.00 mm2 | |
Fault indication | red indicator | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000942 | |
Customs tariff number | 85363030 | |
EAN | 8595090560968 |