Supply (DP and DMP) - with RFi filter
DPF-048DC-16
Order number: A06637visual fault singalling
- surge protection with integrated RFi filter
- installation to LV installations, close to protected equipment
- for protection of control systems, electronic security and fire systems against impact of transient overvoltage and RF disturbance
- for AC or DC power supply
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Type of SPD | T3 | |
VF filter | yes | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 48 V AC |
Maximum operating voltage | Uc | 60.00 V AC |
Maximum operating voltage | Uc | 60.00 V DC |
Nominal load current | IL | 16.000 A |
Maximum overcurrent protection | 16 A gL/gG or C 16 A | |
Filter attenuation at 1MHz (50 ?/50 ?) symmetrical | 45 dB | |
Filter attenuation at 1MHz (50 Ω//50 Ω/) unsymmetrical | 30 dB | |
Test voltage L+ - L- | 4.0 kV | |
Test voltage L+(L-)-PE | 4.0 kV | |
voltage protection level L+ - L- | 0.42 kV | |
voltage protection level L+(L-)-PE | 0.50 kV | |
Response time L+ - L- | 25 ns | |
Response time L+(L-)-PE | 100 ns | |
Connection (input - output) | terminals-terminals | |
Cross-section of connected conductors solid (max) | 6.00 mm2 | |
Cross-section of connected conductors stranded (max) | 6.00 mm2 | |
Fault indication | red indicator | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 80 °C | |
Humidity | 5 - 95 % | |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 | |
ETIM Class | EC000942 | |
Customs tariff number | 85363010 | |
EAN | 8595090566373 |