Combination type - T1 (25 kA)

FLP-25-T1-VSF/4

Order number: A07115

pluggable module, visual fault signalling, module locking, remote fault signalling

  • four-pole high performance lightning current arrester without follow current
  • installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards
  • for protection against impact of direct or indirect lightning strikes in wide range of applications – office and industrial buildings
  • coordination with SPD Type 2 (SLP-275 V) even without surge separating inductors
  • zero leakage current
  • with integrated backup fuse

Technical parameters

Parameter name Parameter value
Type of SPD T1
Mounting DIN rail 35 mm
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260.00 V AC
Type of network TN-S
Maximum overcurrent protection -
Short-circuit current rating ISCCR 50.0 kA
Residual current IPE 0.004 mA
Lightning impulse current (10/350 µs) Iimp 25.00 kA
Voltage protection level Up 1.50 kV
Response time ta 100 ns
TOV 5 s L-N 335 V
TOV characteristic (TOV 5 s) withstand
Cross-section of connected conductors solid (min) 2.50 mm2
Cross-section of connected conductors solid (max) 50.00 mm2
Cross-section of connected conductors stranded (min) 2.50 mm2
Cross-section of connected conductors stranded (max) 35.00 mm2
Cross-section of remote indication conductors solid (max) 1.5 mm2
Cross-section of remote indication conductors stranded (max) 1.5 mm2
Fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250V/0,5A AC,250V/0,1A DC
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
Humidity 5 - 95 %
According to standard EN 61643-11:2012, IEC 61643-11:2011
ETIM Class EC000381
Plug module FLP-25-T1-V/0
Customs tariff number 85363090
EAN 8595090571155

Files for download

  • Product dimensions

  • Basic circuit diagram

Replacement module