Ex environment
ISG-500H Ex
Order number: A04109two M8 bolts with nuts, stainless steel enclosure
- heavy duty encapsulated isolating spark gap for use in Hazardous (Ex) Areas II 2G Ex mb IIC T6 Gb and II 2D Ex mb IIIC T80 °C Db
- for indirect connection (earthing) of isolated conductive parts under lightning conditions
- for safe installation in Ex zone 1 (gas) or 21 (dust)
Technical parameters
Parameter name | Parameter value | |
---|---|---|
Classification | class H - heavy duty | |
Isolation resistance | 100.00 MOhm | |
Lightning impulse current | Iimp | 100.00 kA |
Rated impulse sparkover voltage | Uimp | 1.50 kV |
Rated power frequency withstand voltage | UWAC | 0.350 kV |
Rated DC withstand voltage | UWDC | 0.500 kV |
Degree of protection | IP 67 | |
Range of ambient temperatures (min/max) | -40 / 50 °C | |
According to standard | EN 62561-3, EN 60079-0, EN 60079-18 | |
Explosion-tested version | II 2G Ex mb IIC T6 Gb, II 2D Ex mb IIIC T80°C Db | |
ETIM Class | EC000510 | |
Customs tariff number | 85363090 | |
EAN | 8595090541097 |